Battery runtime calculator: how long will it last?

Enter the battery’s amp-hours and voltage, its type, and what you are running. The calculator uses only the usable part of the battery and adds the inverter loss for AC loads.

Enter your measurements

Total amp-hours of the bank (two 100 Ah in parallel = 200 Ah). Lead-acid: the 20-hour rating.
12 V lead-acid, 12.8 V LiFePO4, 24/25.6 V or 48/51.2 V.
Sets how much of the rated capacity you plan to use: 80% for LiFePO4 (Victron rates cycle life at 80% depth of discharge), 50% for lead-acid (Trojan recommends 20–50% for long life).
Running watts of everything on at once
More options: DoD · Inverter eff. · Duty …
%
Blank uses 80% for LiFePO4 and 50% for lead-acid. Check your battery’s data sheet.
%
Victron puts modern inverters above 90%.
%
For anything on a thermostat. A 12 V compressor fridge runs roughly 25–50% of the time (Victron’s example); a household fridge about a third (Virginia Cooperative Extension).
What the inverter uses just being on, all the time it is on. It matters most for small loads left running 24/7 — a CPAP, Starlink, a fridge.
°F
Batteries hold less when cold: Victron gives about 80% for LiFePO4 at 32 °F (0 °C) and 50% at −4 °F (−20 °C); lead-acid about 86% at 32 °F. LiFePO4 must not be charged below 41 °F (5 °C) unless it is self-heating.
Runtime9.2 hours
In hours and minutes
9 h 13 min
Usable energy
1,024 Wh
Average draw from the battery
111.1 W
Battery current while running
8.7 A
How we got this

100 Ah × 12.8 V × 80% usable = 1,024 Wh

100 W ÷ 90% inverter = 111.1 W average

1,024 Wh ÷ 111.1 W = 9.2 hours (9 h 13 min)

For this job · affiliate link
Battery monitor with shuntA shunt battery monitor shows real amp-hours used, so you know how much of this runtime is left without guessing from voltage.
View on Amazon (opens in a new tab)

Next: how long the sun takes to refill it.

Quick answers for common sizes

Worked examples for the Battery Runtime Calculator
ExampleAnswer
How long a 100Ah battery runs a fridge41 hours — a 12 V compressor fridge (50 W, on half the time) on 100Ah LiFePO4
How long a 100Ah battery lasts with a 1000W inverter55 min at full load (12.8 V LiFePO4)
How long a 200Ah battery lasts with a 2000W inverter55 min at full load (12.8 V LiFePO4)
How long a 100Ah battery runs a CPAP15.4 hours at 60 W (LiFePO4, via inverter)
How long a 100Ah battery lasts with a 200W load4.6 hours (LiFePO4, via inverter)

Runtime at other loads

Runtime at other loads
LoadRuntimeBattery current while running
2536.9 hours2.2 A
5018.4 hours4.3 A
1009.2 hours8.7 A
2004.6 hours17.4 A
5001.8 hours43.4 A
10000.9 hours86.8 A
20000.5 hours173.6 A

Runtime is usable watt-hours divided by the watts the load takes from the battery. Worked examples: how long a 100Ah battery runs a fridge, how long a 100Ah battery lasts with a 1000W inverter, how long a 200Ah battery lasts with a 2000W inverter, how long a 100Ah battery runs a CPAP and how long a 100Ah battery lasts with a 200W load.

The formula

usable Wh = Ah × volts × depth of discharge
watts from battery = load watts ÷ inverter efficiency (AC loads)
hours = usable Wh ÷ (watts from battery × share of time on)

Depth of discharge is the share of the label capacity you plan to use. Victron rates its LiFePO4 batteries for 2,500 cycles at 80% depth of discharge, so 80% is the default for lithium. Trojan recommends discharging lead-acid 20–50% for long life, so 50% is the lead-acid default. Run a lead-acid battery to 80% and you get more hours today and fewer years of battery.

Why real runtime is often shorter

  • High current on lead-acid. Lead-acid capacity is quoted at the 20-hour rate. Trojan’s 27TMX gives 105 Ah over 20 hours, 97 Ah over 10 hours and 85 Ah over 5 hours. The calculator applies a Peukert correction for lead-acid, with an exponent worked out from those ratings (about 1.18 flooded, 1.19 AGM from Trojan’s 31-AES); it shows the on-paper figure alongside.
  • Cold. Victron’s LiFePO4 manual says capacity drops about 20% at 0 °C and about half at −20 °C; Victron’s lead-acid table gives 80% at −10 °C. Set Coldest battery temperature under More options.
  • Inverter idle draw. An inverter uses some power just being switched on. With a small load on a big inverter, that idle draw can be a large share of the total — enter it under More options from the inverter manual’s no-load figure.
  • Age. Both chemistries lose capacity as they cycle; batteries are usually considered worn out at 80% of their original capacity.

Runtime for a 100 Ah battery

Before cold, age and high-current losses. Lead-acid at high loads will come in under this figure.
Load12.8 V LiFePO4 (1,024 Wh usable)12 V lead-acid (600 Wh usable)
25 W DC40 h 58 min24 h
50 W DC20 h 29 min12 h
100 W AC (90% inverter)9 h 13 min5 h 24 min
300 W AC (90% inverter)3 h 4 min1 h 48 min
1000 W AC (90% inverter)55 min32 min

Duty cycle: fridges, freezers and heaters

Anything on a thermostat runs part of the time. The two figures on this site come from two sources and two kinds of fridge: Victron’s book puts a typical 12 V compressor fridge at about 50 W and gives 25–50% duty cycles (about 25–50 Ah a day from a 12 V battery); Virginia Cooperative Extension’s rule for a household fridge is about a third of the time. Use 50% for a 12 V fridge in warm weather as the cautious figure, a third for a household fridge — or measure a whole day with a meter and enter the average under Share of the time the load is on.

RV absorption fridges: run them on propane off-grid

Many RVs have an absorption fridge that runs on propane or on electric. On electric it uses a heating element rather than a compressor — Champion’s chart lists RV refrigerators at 150–600 running watts — and that heat is needed for hours on end, which flattens a battery bank quickly through an inverter. Off-grid, switch it to propane and the battery only runs its controls; save electric mode for shore power or a generator. This calculator’s fridge figures are for compressor fridges.

CautionLithium batteries: keep terminals covered, never short them, and charge only within the temperature range on the data sheet — Victron’s LiFePO4 batteries must not be charged below 5 °C. Wire and fuse sizes come from NEC/ABYC ampacity tables and the equipment manual — have a qualified installer check them.
CalculatorBattery Bank Size Calculator →Need a bigger bank? Size it from your daily watt-hours and days without sun.

What you’ll need

  • Battery monitor with shuntMid-range price

    Counts amp-hours in and out, so you see true state of charge instead of guessing from voltage — which barely moves on a LiFePO4 battery until it is nearly empty.

    See options on Amazon (opens in a new tab)
  • 12 V 100 Ah LiFePO4 batteryPremium price

    About 1.28 kWh rated in a box roughly the size of a group 24–31 lead-acid battery at around half the weight. Check the BMS discharge limit and whether it can charge below freezing.

    See options on Amazon (opens in a new tab)
  • Inline DC watt meterBudget price

    Sits between a 12 V device and its supply and shows watts, amps and watt-hours used — handy for measuring a 12 V fridge, Starlink Mini or fan.

    See options on Amazon (opens in a new tab)

As an Amazon Associate we earn from qualifying purchases. Links to products are affiliate links — they cost you nothing extra and help keep these calculators free.

Frequently asked questions

How long will a 100Ah battery last?

A 12.8 V 100Ah LiFePO4 battery has about 1,024 Wh usable, so it runs a 100 W DC load about 10 hours, or a 100 W AC load through a 90% inverter about 9.2 hours. A 12 V 100Ah lead-acid battery has about 600 Wh usable — a bit over half as long. See how long a 100Ah battery lasts with a 200W load.

How long will a 12V battery run a fridge?

A 12 V compressor fridge averaging 25 W (50 W running half the time) runs about 41 hours on a 100Ah LiFePO4 battery and about 24 hours on a 100Ah lead-acid battery used to 50%. See how long a 100Ah battery runs a fridge.

How long will a 200Ah battery last with a 2000W inverter?

At a full 2,000 W load, about 55 minutes from a 12.8 V 200Ah LiFePO4 bank — and it would be drawing about 174 A. See how long a 200Ah battery lasts with a 2000W inverter.

Does a bigger inverter drain the battery faster?

Only the load you run sets the drain — but a bigger inverter has a higher idle draw, which matters when it is left on with little or nothing plugged in.

Can I use 100% of a LiFePO4 battery?

The battery’s management system will let you go close to empty, but cycle life falls the deeper you go. Victron rates 2,500 cycles at 80% depth of discharge and 5,000 at 50%, which is why sizing here uses 80% by default.