Battery bank size calculator

Enter what the battery has to supply — a day’s watt-hours, or an inverter load for a set time — and the battery type. You get the bank size in amp-hours and how many 100 Ah-class batteries make it up.

Enter your measurements

Watt-hours a day, inverter losses included — the total from the solar load calculator.
Days the bank must cover with no charging. One for a van with solar; two or three for a cabin through cloudy spells.
Sets how much of the rated capacity you plan to use: 80% for LiFePO4 (Victron rates cycle life at 80% depth of discharge), 50% for lead-acid (Trojan recommends 20–50% for long life).
For counting batteries. 100 Ah is the common size; lead-acid: use the 20-hour rating.
More options: DoD · Battery temp
%
Blank uses 80% for LiFePO4 and 50% for lead-acid. Check your battery’s data sheet.
°F
Batteries hold less when cold: Victron gives about 80% for LiFePO4 at 32 °F (0 °C) and 50% at −4 °F (−20 °C); lead-acid about 86% at 32 °F. LiFePO4 must not be charged below 41 °F (5 °C) unless it is self-heating.
Battery bank needed195 Ah12 V
Made up of
2 × 100 Ah 12.8 V in parallel
Batteries
2 batteries · LiFePO4
Energy the bank must deliver
2,000 Wh
Rated energy of that bank
2,560 Wh
How we got this

2,000 Wh × 1 day = 2,000 Wh

2,000 Wh ÷ 80% usable ÷ 12.8 V = 195 Ah = 195 Ah

195 Ah ÷ 100 Ah per battery → 2 × 100 Ah 12.8 V in parallel

Before you wire itWire and fuse sizes come from NEC/ABYC ampacity tables and the equipment manual — have a qualified installer check them.

For this job · affiliate link
12 V 100 Ah LiFePO4 batteryBuy matching batteries — same make, model and age — so they share the load evenly in parallel.
View on Amazon (opens in a new tab)

Next: size the solar array to refill it.

Quick answers for common sizes

Worked examples for the Battery Bank Size Calculator
ExampleAnswer
What size battery bank for a 3000W inverter326 Ah of 12 V LiFePO4 for an hour — 4 × 100 Ah
What size battery bank for a 2000W inverter217 Ah of 12 V LiFePO4 for an hour — 3 × 100 Ah

Bank size for other days of autonomy

Bank size for other days of autonomy
Days of autonomyBattery bank neededBatteries
0.598 Ah1 battery
1195 Ah2 batteries
2391 Ah4 batteries
3586 Ah6 batteries
5977 Ah10 batteries

Sizing for an inverter rather than a day’s use? Worked examples: what size battery bank for a 3000W inverter and what size battery bank for a 2000W inverter.

How the battery bank is sized

energy needed (Wh) = Wh per day × days of autonomy
   (or inverter watts ÷ efficiency × hours)
bank Ah = energy needed ÷ usable depth of discharge ÷ bank voltage
batteries = (system V ÷ 12) in series × (bank Ah ÷ Ah per battery) in parallel

The depth of discharge is what turns a lithium bank and a lead-acid bank of the same label size into very different things. Victron rates its LiFePO4 batteries for 2,500 cycles at 80% depth of discharge and 5,000 at 50%; Trojan recommends discharging lead-acid only 20–50% for best life. So, by default, this calculator plans to use 80% of a lithium bank and 50% of a lead-acid one — a lead-acid bank has to be about 1.6 times bigger in amp-hours for the same job.

Days of autonomy

Autonomy is how many days the bank covers with no charging at all — cloudy days, a generator that won’t start. More days means a much bigger, more expensive bank, so many systems pair one or two days of battery with enough solar to refill it and a generator or charger for long cloudy spells.

At 80% usable for LiFePO4, 50% for lead-acid. Divide by 2 for a 24 V bank, by 4 for 48 V.
Daily use1 day, LiFePO4 12.8 V2 days, LiFePO4 12.8 V1 day, lead-acid 12 V
500 Wh49 Ah98 Ah83 Ah
1,000 Wh98 Ah195 Ah167 Ah
2,000 Wh195 Ah391 Ah333 Ah
3,000 Wh293 Ah586 Ah500 Ah
5,000 Wh488 Ah977 Ah833 Ah

Big inverters: current can matter more than energy

A large inverter on a 12 V bank pulls hundreds of amps. Victron recommends keeping continuous discharge on its 12.8 V 100 Ah LiFePO4 at or below 100 A (1C), with a 200 A maximum. So a 3,000 W inverter at full load — about 260 A from 12.8 V — needs at least three such batteries in parallel even if one would hold enough energy for the job. The inverter-mode result checks this and raises the battery count when current, not watt-hours, is the limit.

Series and parallel

  • Series adds voltage. Two 12 V batteries in series make 24 V at the same amp-hours; four make 48 V.
  • Parallel adds amp-hours. Two 100 Ah batteries in parallel make 200 Ah at 12 V.
  • Match them. Same make, model, capacity and age. Mixing old and new, or lithium and lead-acid, makes some batteries work harder than others.
  • Lithium limits. Check the battery manual for the maximum number in series and parallel; it depends on the battery’s management system.

Battery sizes by group number — 24, 27, 31 — and their amp-hours are in the battery group size chart; the chemistry trade-offs are in LiFePO4 vs lead-acid.

CalculatorSolar Panel Calculator →Now size the panels that refill this bank every day.

What you’ll need

  • 12 V 100 Ah LiFePO4 batteryPremium price

    About 1.28 kWh rated in a box roughly the size of a group 24–31 lead-acid battery at around half the weight. Check the BMS discharge limit and whether it can charge below freezing.

    See options on Amazon (opens in a new tab)
  • 12 V deep cycle AGM batteryMid-range price

    Sealed lead-acid with no watering. Cheaper up front than lithium, but plan to use only about half its rating and expect it to weigh roughly twice as much.

    See options on Amazon (opens in a new tab)
  • Battery monitor with shuntMid-range price

    Counts amp-hours in and out, so you see true state of charge instead of guessing from voltage — which barely moves on a LiFePO4 battery until it is nearly empty.

    See options on Amazon (opens in a new tab)
  • Vented battery boxBudget price

    Covers the terminals so a dropped tool can’t short them and keeps a lead-acid battery’s spills contained. Flooded batteries need the vent.

    See options on Amazon (opens in a new tab)

As an Amazon Associate we earn from qualifying purchases. Links to products are affiliate links — they cost you nothing extra and help keep these calculators free.

Frequently asked questions

How many batteries do I need for solar?

Divide your daily watt-hours by the usable energy per battery. A 12.8 V 100 Ah LiFePO4 battery gives about 1,024 Wh usable; a 12 V 100 Ah lead-acid about 600 Wh. So 2,000 Wh a day for one day takes two lithium or four lead-acid batteries.

What size battery bank do I need for a 3000W inverter?

At full load for an hour, about 325 Ah at 12.8 V of LiFePO4 — four 100 Ah batteries — and at least three in parallel just to carry the current. See what size battery bank for a 3000W inverter.

Should I build a 12 V, 24 V or 48 V battery bank?

Twelve volts suits vans and small RVs with 12 V appliances. Above a couple of kilowatts of inverter, 24 V or 48 V halves or quarters the current, which makes cabling, fusing and battery current limits far easier to live with.

How many days of autonomy do I need?

There is no single answer: one day for a van that drives and charges, two or three for a cabin that relies on solar alone, plus a generator or charger for long cloudy spells. Every extra day adds a full day’s worth of battery.