Starting watts vs running watts

Every generator and inverter lists two power ratings, and every appliance with a motor has two power draws. Mixing them up is the most common reason a generator stalls when the fridge kicks on — or why people buy one twice as big as they need.

The two numbers

  • Running watts (also continuous or rated watts) — what the appliance draws while it works, and what a generator or inverter can supply for hours.
  • Starting watts (also surge or peak watts) — the brief extra a motor or compressor needs for a moment to get moving, and the short burst a generator or inverter can supply on top of its running rating.

Champion’s 3500 W dual-fuel generator, for example, is rated 3,500 running and 4,000 starting watts on gasoline. Its 2000 W inverter generator is 1,700 running and 2,000 starting. On propane both ratings are lower.

Which appliances have starting watts

Champion Power Equipment’s generator wattage chart (coffee maker: Virginia Cooperative Extension nameplate range).
ApplianceRunning WStarting W
Refrigerator150–400800–1,200
Freezer100–500500–1,000
Sump pump, ½ hp800–1,0501,300–2,150
Well pump, 1 hp1,000–2,0002,000–4,000
Window AC, 10,000 BTU900–1,2001,800–2,400
RV AC, 13,500 BTU1,500–2,0002,800–3,500
Circular saw, 7-1/4 in1,200–1,8002,400–3,600
Air compressor, 1 hp1,5004,500
Space heater750–1,500no extra
Microwave600–1,200no extra
Coffee maker900–1,200no extra

Resistive loads are simple by comparison: a 1,500 W heater draws a steady 12.5 amps at 120 volts from the moment it is switched on until it is switched off, with no surge at all. That is also why a heater can share a generator with a fridge more easily than a second compressor can — its draw never spikes, so it only adds to the running total. Plan generator and inverter sizes so the running total plus one start still fits, and keep heaters on their low setting when a compressor is about to cycle on.

The pattern: anything with an electric motor or compressor surges; anything that just heats, lights or runs electronics doesn’t. The full list is in the appliance wattage chart.

How to add them up

running watts needed = sum of all running watts
starting watts needed = sum of all running watts + the largest single (starting − running)

You add every running load, but only one start — the biggest — because two motors rarely start in the same instant, and you can make sure they don’t by switching things on one at a time, biggest first.

Running total 1,370 W; starting requirement 1,370 + 1,100 = 2,470 W.
LoadRunning WStarting WStart-up extra
Refrigerator2001,2001,000
Sump pump, ½ hp1,0502,1501,100
Lights and router120——
Total1,370largest: 1,100

So a generator rated at least 1,370 running and 2,470 starting watts runs this set, and more running headroom makes it work less hard. Adding all the starting watts together instead (3,350 + lights) would oversize it. The generator size calculator does this for any list; what size generator to run a refrigerator and what size generator to run a well pump are worked examples.

Inverters work the same way

A battery inverter also has a continuous rating and a surge rating, and the surge figure is what starts a fridge or pump. The surge may last only a moment, so check the spec sheet for how long it is held. What size inverter for a refrigerator shows why a fridge running on 200 W can still need a 1,000 W-class inverter.

Reducing starting watts

  • Start the biggest motor first, with everything else off, then add loads.
  • Soft-start devices for air conditioners and some pumps reduce the start surge; check the maker’s figures for your model.
  • Stagger thermostats so two compressors don’t cycle on together.
  • Don’t confuse starting watts with daily energy. The surge lasts seconds, so it barely affects fuel or battery capacity — it only sizes the generator or inverter.
CautionRun generators outdoors only — CPSC says at least 20 feet from your home or RV, away from doors, windows and vents — and never plug one into a house outlet. See the generator safety guide.
CalculatorGenerator Size Calculator →Add up your own running and starting watts.

Frequently asked questions

Do I need to add starting watts together?

No — add all the running watts, then only the largest single start-up extra, and start motors one at a time.

Does a microwave have starting watts?

Champion’s chart lists no extra starting watts for a microwave; size on its input (running) watts from the label.

How long do starting watts last?

Only a moment, while a motor comes up to speed — which is why a generator or inverter can supply it briefly above its running rating.